en
Measuring ranges: Ambient model: -20 to +80°C and terminal block model: from -100 to +400°C
With or without 2-line 19-digits LCD display
Two relays
0-5/10 V or 0/4-20 mA outputs
Quick and easy mounting with the 1/4 turn system with wall-mount plate
Adjustment certificate
Product info
Measure details
-
Units°C
Technical details
-
ParametersTemperature
-
Displays2-line display
-
IP ProtectionIP 65
-
StandardsUKCA2011/65/EU RoHS II2012/19/EU WEEE2014/30/EU EMC2014/35/EU Low Voltage
-
Power supply24 Vac/Vdc
-
Outputs2 x 4-20 mA or 2 x 0-20 mA or 2 x 0-5 V or 2 x 0-10 V (4 wires)
-
Relay2 changeover relays 3 A / 230 V
-
Ethernet communicationNo
-
ModBus networkNo
Instrument Dimensions
-
Length125 mm
-
Width59.2 mm
-
Height115 mm
-
Weight340 g
Operating temperature
-
Min-10.00 °C
-
Max50.00 °C
Storage temperature
-
Min-10.00 °C
-
Max70.00 °C