Understanding and choosing a condensate pump

A condensate pump has a detection part located in a tank where the condensate flows. Above a certain level, the condensate triggers the pump, which sucks it up and lifts it to a drainage circuit. It is needed whenever the condensate cannot drain away by gravity alone.

By avoiding condensate leaks, a pump helps prevent breakdowns, water damage, electrical problems, rust and mould, which can spread through the ventilation ducts and into the ambient air. It therefore helps preserve the building, the life and efficiency of the heating, air conditioning or refrigeration system, and indoor air quality.

For each type of system there is a type of pump to be preferred:

  • Mini pumps: for low to medium capacity air conditioning (console, split, cassette, domestic or tertiary), for units up to about 20 kW. They are designed to be integrated discreetly and silently, with a small detection tank that is sometimes external to the pump unit.

  • Tank pumps: for more powerful systems that produce more condensate, sometimes of a more aggressive nature, such as the hot, acidic condensate of combustion boilers. The detection part is contained in a large tank attached to the pump block. Power and resistance are the priorities.

  • Peristaltic pumps: roller pumps that press a flexible tube to drive the fluid, with no contact with any component outside the circulation circuit. They are small and quiet, and an alternative to mini pumps for individual air conditioning systems and decentralised ventilation units.

  • Refrigerated display case pumps: tank pumps shaped as flat as possible to fit under the refrigerated (fresh or frozen) shelves of supermarkets.

The choice depends on the system in which the pump will be installed:

  • Type of unit: split, ducted, floor-standing, cassette, boiler, refrigerated display case, etc.

  • Power of the heating or cooling system, which determines the quantity of condensate. Climate also matters: in a humid climate the quantity of condensate can be double that of a dry climate.

  • Nature of the condensate: polluted and greasy in a kitchen or hairdresser's, acidic for boilers.

  • Available space, which determines the shape and size of the pump, and where it will be placed (next to, below, inside or remotely above the unit).

  • Type of room, which determines the trade-off between noise and power.

  • Maintenance: not all pumps are easy to detach and clean.

Sauermann has made condensate removal pumps for over 40 years. Five qualities set its mini pumps apart:

  • Made in France: the whole production chain, from design to manufacture, is at the Chevry-Cossigny factory (Seine-et-Marne), with an in-house R&D team located on the test and manufacturing lines.

  • Patented Dual Wave pump core: it uses two phases of alternating current to control the piston movement, which preserves the components, reduces vibrations and noise, and improves energy efficiency.

  • 100% tested pumps: each pump core is assembled and tested automatically for tightness and pumping performance, and each pump is tested for start-up.

  • Simplified maintenance and spare parts: quick access to components, a remote detection unit that is easy to clean or replace, and a range of spare parts.

  • Minimum return rate: backed by a 36-month warranty on condensate pumps.

Start from your system. Mini pumps and peristaltic pumps both serve air conditioning units: mini pumps cover units up to about 20 kW (up to 30 kW with the Si-33), while peristaltic pumps such as the Si-50, Si-51 and Si-52 are designed for air conditioners up to 8 kW. Tank pumps are for larger heating, refrigeration and central air conditioning systems, and for boilers. Refrigerated display cases in supermarkets have their own flat tank pumps.

See the questions on each pump family for details.

Mini condensate pumps

A mini condensate pump is a small, electrically powered pump designed to lift condensate water from the indoor unit to a suitable drainage point. It is typically installed inside or near the indoor unit of a mini-split system. Sauermann mini pumps are also suitable for ducted and console units.

  1. Condensate collection: as the unit cools the air, moisture condenses on the evaporator coil and drips into a drain pan.

  2. Float switch detection: a float switch inside the pump or reservoir detects the water level. When the water reaches a certain height, the float rises and activates the pump.

  3. Pump activation: the pump turns on and pushes the water through tubing to a drain point (outside, into a sink or a drain pipe).

  4. Automatic shut-off: once the water level drops, the float switch lowers and turns off the pump. The cycle repeats as needed.

  • It allows mini-split units to be installed without gravity drainage.

  • It prevents water overflow and potential damage.

  • It is compact and quiet.

  • It includes alarm features.

  • Inline pumps fit inside any type of air conditioning unit or lineset cover and are ideal for concealed installations (for example the Si-20).

  • Wall-mounted pumps are mounted externally near the mini-split unit and are easier to access for maintenance (for example the Omega Pack 2 or the Delta Pack).

  • Remote reservoir pumps have a separate reservoir and pump body, which offers flexible placement (for example the Si-30 or the Si-33).

The Si-27 and the Si-30 are suitable for air-conditioning units up to 20 kW. The high-capacity Si-33 (30 l/h) is suitable for units from 20 kW up to 30 kW. Check the technical specifications of each pump before choosing.

In laboratory tests according to ISO 3744, Sauermann mini pumps are among the quietest on the market. The Si-20 measures 19 dB(A), the Si-30 and the Si-27 measure 20 dB(A), the Si-10 Univers'L 22 dB(A) and the Si-33 34 dB(A). For comparison, a refrigerator is around 38 dB(A).

These values are measured on a suspended pump, isolated from its surroundings. In a real installation, the noise also depends on the vibration of the bracket, the power cable and the flexible tubes.

Preventing even the slightest vibration from travelling through the installation is the number-one priority.

  • Location: the best option is behind the wall where the split system is located, above the ceiling or in the attic space (but not outside the building). Next best is the false ceiling inside the room. Avoid placing it near the split system in a quiet room.

  • Mounting: hang the pump using the anti-vibration mounting bracket. Avoid fixing it to plasterboard, plastic trunking or a metal pipe without the bracket.

  • Cable and tubing: wrap the power cable and flexible tubing in insulating foam and keep the tubing away from other surfaces. Avoid leaving them exposed next to a wall or ceiling.

Sauermann piston pumps also prevent hydraulic noise: the detection system stops the pump sucking air with the condensate, and the Y-shaped Drain Safe Device means the pump never sucks air at start-up.

Peristaltic condensate pumps

A flexible hose is compressed by one or more rollers attached to a rotor. This compression pushes the fluid inside the hose towards the outlet, while the released portion of the hose returns to its shape, creating suction that draws liquid in from the inlet.

The fluid never comes into contact with the mechanical parts. Regular replacement of the hose and maintenance of the rollers ensure optimal performance and a long equipment life.

Peristaltic pumps are an alternative to mini condensate pumps. They perform the same functions but are designed for individual air conditioning systems and decentralised ventilation units. They are small, quiet and produce no vibration.

The choice depends on two critical factors: the required flow rate and delivery head, and the installation environment, which can determine the choice of detection mode. The Si-50, Si-51 and Si-52 suit common air conditioners up to 8 kW (wall units, air conditioning cabinets, ceiling units) with a constant discharge of up to 12 m. Consult the technical specifications of each pump.

  • Power: suitable for common air conditioners up to 8 kW, with a constant discharge of up to 12 m (Si-50, Si-51, Si-52).

  • No vibration: operation does not produce vibration.

  • Reliable activation: three activation modes (compressor signal, temperature differential or float) reduce the risk of failure.

  • Simplified maintenance: the hose can be replaced without tools, and maintenance is done outside the air-conditioned room.

  • Robustness: increased resistance to moisture, dust and slurry fluids.

Tank pumps

Tank pumps are made for large heating, refrigeration and central air conditioning systems that produce substantial amounts of condensate, sometimes of a more aggressive nature (such as the hot, acidic and polluted condensate of combustion boilers). Their detection part is contained in a large tank attached to the pump block. They are powerful, hard-wearing pumps built to last.

  • Si-82 (centrifugal): easy to install whatever the layout, evacuates up to 500 l/h.

  • Si-83: redesigned from the inside out to be more compact than any other tank pump in its class.

  • Si-60: piston pump with built-in tank (0.37 l) for air-conditioning units up to 20 kW.

  • Si-1805: compact centrifugal pump, 500 l/h, for gas condensing boilers (the bare-ends version is for air conditioning units and refrigerated display cabinets).

  • Si-1822: large tank pump for heavy and contaminated condensate, up to 380 l/h.

  • Si-1850: large tank pump for hot water and heavy, contaminated condensate, up to 1100 l/h.

  • Si-2052: replaces some market-standard drain pumps in cassette-type air-conditioning units up to 20 kW.

See each product page for the full specifications.

The Si-1830 is a centrifugal tank pump with IPX4 protection, designed to process acidic (pH > 2) and high-temperature condensate. The Si-1805 is designed for gas condensing boilers. For gas boilers, the Pressure Safe System allows a safe discharge of condensate and of pressure relief valve water.

Supermarket condensate pumps

Pumps for refrigerated display cases serve the chiller, freezer and deep-freeze departments of supermarkets, and are often called dairy pumps. They have to discharge large quantities of condensation and cleaning liquid while remaining reliable and robust. Their slimline design lets them be placed under refrigerated shelves, and they are often combined with a solution that prevents biofilm formation. They suit stores of all sizes, from the local convenience store to the large supermarket.

Leaks are most often overflows from a condensate drainage system blocked by pollution (particles, algae, biofilm, sludge). The most common cause is biofilm, which often clogs the drainage tubes upstream of the pump. The Si-1931 combined with Gel-clear tablets prevents biofilm.

  • Reduces condensate leaks in chilled and frozen food aisles by 95%.

  • The Si-1931 is only 8 cm high, so it slides under display cabinets. It has an easy-open cover and a single debris filter, and is made entirely of stainless steel.

  • One tablet can keep condensate pipes free of blockages for up to a year. The tablet is replaced every six months or every year depending on climate and cabinet size, and can be inserted while the unit is running.

  • The tablet is certified non-corrosive for metal, non-aggressive for pumps and fully water-soluble, and the formula is approved by NSF International for use in food preparation zones.

Installation and connection

Some condensate pumps are relatively simple to install, but we strongly recommend calling in a professional to make sure the pump works properly and to avoid any risk, especially electrical. Always switch off the unit before installation.

  1. Turn off the unit before installation.

  2. Check voltage compatibility to avoid electrical issues.

  3. Secure the tubing with metal clips or zip ties to prevent leaks.

  4. Install anti-siphon devices to avoid backflow.

  5. Test the pump by filling the reservoir with water to confirm it activates.

Installation videos are available in the Resource centre.

The alarm prevents an excessive build-up of condensate, guarding against leaks and overflows that can cause severe water damage and electrical damage. With a mini pump on an air conditioning unit, the detection unit contains a float that, at its maximum level, triggers a circuit-breaker that cuts the power supply to the split (normally closed alarm circuit). On a boiler, a normally open circuit triggers an audible or visual warning instead, so that heating and hot water are not lost.

The alarm protects you if the pump stops working, if it is under-powered, or if the drain pipe is blocked, fouled or pinched. It also matters for the installer: if a leak causes water damage, the insurer may hold the installer liable if the alarm was not installed to the manufacturer's specifications.

The alarm circuit sits on the phase line of the air conditioner's power supply. The brown "L" wire coming from the outdoor unit powers the pump. The pump passes power back to the indoor unit from the grey "C" wire to the black "NC" wire, through the alarm circuit breaker controlled by the float.

If the air conditioner manufacturer does not allow the pump to be powered from the outdoor unit, set up an independent power supply for the pump but still connect the black "NC" return wire to the indoor unit, so that the alarm works. Because the pump keeps its own supply, it can empty the tank after the alarm trips, and the indoor unit restarts once the float falls back.

A detailed wiring diagram, including connection instructions for VRF air conditioning units, comes with every Sauermann mini pump. Electrical connections should be made by a qualified professional.

  1. Clean the condensate tray of any debris left over from manufacturing or from unpacking the unit.

  2. Pour a little water into the tray (a squeezable plastic bottle works well). Add small amounts at a time rather than a full bottle at once.

  3. Check that the pump starts and then stops as the water level decreases.

  4. Check the safety switch by continuing to pour water until the alarm triggers (cutting off the compressor).

  5. Also test that the pump removes the water when the air conditioner is switched off.

Maintenance and cleaning

We recommend calling in a professional about once a year, and more often when the pump is exposed to air loaded with particles (flour in a bakery, for example). Check your air conditioner before summer: the mini pump can even foul over winter, when the unit is in heating mode and the pump is out of use.

For a mini pump, clean the reservoir and filter every 3 to 6 months and inspect the wiring and tubing for wear or leaks. The detection unit should be cleaned at the beginning of the season and regularly if the system is used all year round. You can also inspect the detection system and the (often transparent) drain tubes for dirt.

Biofilm is the leading cause of fouling in a condensate pump, and it is impossible to avoid completely. Depending on where the unit is located, other causes include:

  • dust and particles suspended in the air;

  • aerosols and lacquers (for example in hair salons);

  • cellulose (paper) dust, for example in libraries and bookshops;

  • tobacco smoke;

  • smoke from cooking oils and fats, especially in open-plan kitchens.

A float-type detection unit is especially sensitive to fouling: the float can stick to biofilm that has dried out over the winter, and then the pump does not start and leaks can begin.

  1. Switch off the power supply to the air conditioner, but keep the power to the pump on so that you can test it.

  2. Check the pump: use a burette to distribute water evenly over the heat exchanger and into the tray below. With a transparent tank, empty it to watch the pump work; otherwise listen for the sound it makes as it starts. A leak suggests that the pump is excessively fouled or broken.

  3. Open the detection unit tank and rinse it with the cleaning solution (or water) to remove all particles. Make sure the bottom of the tank is not sticky, and that the float is clean and slides smoothly. The same procedure applies to capacitive detection systems.

  4. Re-insert the detection unit and check again that it works correctly.

Reaching the detection unit is often tricky, as it can involve detaching the unit from its wall mount: this is a job for a professional. The Delta Pack and Omega Pack make access much easier, with the pump in easy-open trunking and a transparent tank that shows fouling at a glance.

You can buy special pump cleaning products from distributors. If you cannot get a specialist product, use a solution of 5% bleach in water (ideally demineralised).

Important: never use petroleum products or solvents such as acetone, which destroy plastic parts and especially rubber (pump seals and central mechanism). White vinegar is of limited use because condensate is mineral-free, so no limescale forms.

A condensate pump can last for years if it is properly maintained. Replacement is recommended after a severe breakdown or when the pump is in an advanced state of wear, which a professional can anticipate, in particular by assessing the noise the pump makes in operation.

Yes. Sauermann offers a range of spare parts for mini pumps to extend their life and avoid unnecessary waste. The detection unit is designed to be quick to clean or replace without dismantling the whole pump, and the float of the sensor can be replaced on its own. Kits of 5 new floats for all our detectors are available from your distributor (references ACC00947 or ACC00946).

Troubleshooting

First, have your air conditioning system serviced by a professional every year, ideally after winter. These ten checks help prevent a leak, or troubleshoot one:

  1. The unit is fitted with a suitable condensate pump (enough power for the length of the drain tubes and enough flow for the condensate produced).

  2. The unit and the pump detection system are perfectly horizontal (check with a spirit level).

  3. The pump is not installed somewhere that gets too hot in summer (for example an attic with poor insulation), as its thermal safety can switch it off.

  4. The drain tube is not blocked (insects, spiders or biofilm).

  5. The drainage system has been cleaned after winter, including the detection system.

  6. The drain tubes are not pinched or twisted.

  7. The pump works properly, even when the air conditioner is switched off, and its alarm is properly connected to the unit.

  8. All joints upstream and downstream of the pump are secured with clamps and watertight.

  9. The refrigerant gas circuit is properly insulated, so that no frost forms on the copper tubes.

  10. The fins and dust filters are not clogged, which could cause frost and then a leak when it melts.

Check the wiring and the power supply. For all problems, also check that:

  • the discharge lines are neither obstructed nor kinked;

  • the float inside the detection unit is not blocked;

  • the hydraulic inlets and outlets are not obstructed.

If the pump runs for more than one minute, check that the discharge height is within the limit of the pump and that the pump suits the capacity of the air conditioning unit.

If the pump runs continuously but does not suck in any water, check that the suction hose between the pump and the detection unit is connected and airtight. If it is, the pump itself may be faulty and can be returned under warranty if it is covered.

Check that the detection unit is mounted level. Then turn the pump off and see whether the water returns down the discharge line: if it does, replace the pump. Before you start cleaning your air conditioning system, remove the pump to prevent damage.

Dried biofilm can stick the float to its mount, especially after the unit has been out of use over winter. Clean the detection unit as described in the cleaning question, making sure the bottom of the tank is not sticky and the float slides freely. If the float is damaged, kits of 5 new floats are available from your distributor (references ACC00947 or ACC00946).

The alarm only triggers when there is a real condensate removal problem. If the split is permanently disabled, the pump is malfunctioning or the drain pipes are blocked. If the split runs intermittently, the pump is under-powered or the drain pipes are partially blocked or pinched. Check the drain tubes first, then the pump, and if necessary replace the pump with a more suitable model.

Most of the noise comes from vibrations travelling from the pump to its bracket, power cable and flexible tubes. See "How can I reduce the noise of a mini pump?" in the Mini condensate pumps section for the best locations, mounting and cable management.

Warranty, service and where to buy

Sauermann condensate removal pumps are covered by a 36-month guarantee. Other Sauermann Industrie products are covered by a 12-month contractual guarantee, and manifolds and instruments in the distribution range by a 24-month guarantee. The guarantee periods start from the date of the invoice. See the Warranty page for the full conditions.

The guarantee does not apply to damage caused by improper use, improper monitoring or maintenance, normal wear and tear or force majeure, nor to consumables and wear parts. It is limited to a credit note for the price paid or a like-for-like replacement. The guarantee should first be claimed from the installer or distributor from whom the product was purchased.

Sauermann pumps are sold through distributors. Use the interactive "Where to buy" map to find your nearest Sauermann condensate pump distributor or to ask about prices.

For any other after-sales question about our pumps, contact your distributor. For calibration, repair, on-site intervention, technical assistance or document requests on instruments, use the Customer Portal: sign in or create your account to access our service offers. You can also use the Contact page of the website.

Heating applications

Combustion boiler systems produce condensate that is more acidic than the condensate of an air conditioner, very hot and polluted with certain substances from the combustion process. When this condensate cannot drain away to a drainage circuit by gravity alone, a condensate pump detects it in a tank and lifts it to the drain.

Avoiding condensate leaks protects the boiler and the building from water damage, electrical problems and rust.

  • Si-61: piston pump in a neutral white colour with a built-in tank (0.37 l), designed to remove acidic condensate from gas condensing boilers up to 50 kW. Its small size and low noise level make it suitable for installation in a kitchen or living space.

  • Si-1805: compact centrifugal tank pump for gas condensing boilers, up to 500 l/h. It tolerates charged, high-temperature and acidic condensate (pH > 3.4).

  • Si-1850: large tank pump for heavy and contaminated condensate, up to 1100 l/h. It also tolerates charged, high-temperature and acidic condensate (pH > 3.4).

  • Si-83: compact tank pump for heating units up to 40 kW, with a smartphone app that makes installation simple.

  • Si-82 Pack 2: the heating version of the Si-82 centrifugal pump, up to 500 l/h.

  • Si-1830: centrifugal tank pump with IPX4 protection, designed to process acidic (pH > 2) and high-temperature condensate.

See each product page for the full specifications.

On a boiler, the pump alarm does not cut the power supply to the boiler, which would mean an inconvenient loss of heating and hot water. Instead, a normally open alarm circuit closes to power an audible or visual warning when the condensate level gets too high.

The Pressure Safe System is designed for gas boilers. It allows a safe discharge of condensate and of pressure relief valve water.

We recommend calling in a professional about once a year. You can also inspect the detection system and the (often transparent) drain tubes for dirt.

Air conditioning applications

When an air conditioner cools the air, moisture condenses on the evaporator coil and drips into a drain pan. If this condensate cannot be evacuated by gravity, a pump lifts it to a suitable drainage point. A pump allows mini-split units to be installed without gravity drainage, and prevents water overflow and the damage it can cause.

  • Up to 8 kW (wall units, air conditioning cabinets, ceiling units and ducted units): peristaltic pumps Si-50, Si-51 and Si-52, with a constant discharge of up to 12 m.

  • Up to 20 kW (console, split and cassette units): mini pumps Si-20 (slim casing that fits inside any unit or lineset cover), Si-27 and Si-30 (piston technology).

  • From 20 kW up to 30 kW: the high-capacity Si-33 (30 l/h).

  • Tank pumps: the Si-83 for residential air conditioning up to 20 kW, the Si-60 (piston pump with built-in 0.37 l tank, up to 20 kW), and the Si-2052, which replaces some market-standard drain pumps in cassette units up to 20 kW.

See the technical specifications of each pump before choosing.

  • Under a wall-mounted unit: the Omega Pack 2 (all-in-one, ready-to-fit kit for mini-split units) or the Delta Pack (complete kit with an elbow that opens by hand with a finger push).

  • Hidden inside the unit or lineset cover: the Si-20, or the Si-21 Silent Flow, whose slim design fits inside any type of air conditioner or trunking.

  • Tight spaces: the Si-10, with an integrated detection unit.

  • Separate reservoir and pump body: the Si-30 or the Si-33.

  • Replacing an existing pump: the Si-10 Univers'L, a universal replacement pump for new installations and refurbishments, or the Si-2052 for cassette units.

The Si-21 Silent Flow is designed for bedrooms and offices. After operating at high flow rates during the first cycles, it adapts its performance to the real needs of the system and then runs in its silent mode.

In laboratory tests (ISO 3744), the Si-30 measures 20 dB(A). Peristaltic pumps produce no vibration. See "How can I reduce the noise of a mini pump?" for installation tips that limit noise.

Connect the pump alarm. When the float in the detection unit reaches its maximum level, it triggers a circuit-breaker that cuts the power supply to the air conditioner, so the unit stops producing condensate. On the Si-52, the safety contact automatically stops the compressor or the solenoid valve.

An alarm that has not been connected can also make the installer liable if a leak causes water damage. See "Why should I connect the pump alarm?" for details.

Yes. In heating mode, the condensate flows to the outdoor unit and the drainage system of the indoor unit is not used. The mini pump is then out of use, and the biofilm in the detection unit can dry out and stick the float. Have the system serviced by a professional every year, ideally after winter, and check the pump before summer.

  • A pump that is not suited to the unit or to the length of the drain tubes.

  • A unit or detection unit that is not level.

  • A blocked or pinched drain tube.

  • A dirty detection unit, or a float stuck by biofilm.

  • Loose or leaking joints.

  • Clogged fins or dust filters, or poorly insulated refrigerant tubes, which lead to frost and then to a leak when it melts.

See the Troubleshooting section for the full list of checks.

Refrigeration applications

Open display cabinets produce abundant condensation. They are often placed in the middle of the store, so a powerful pump is needed to evacuate the condensate over long distances. The cabinets run 24 hours a day, 365 days a year, and the condensate carries particles and organic matter that can clog the drainage circuit. A failure puts the cold chain at risk and creates a slip hazard in the aisle.

  • Si-1931: ultraflat pump designed to handle condensate from supermarket refrigerated display cabinets, supplied with a Gel Clear tablet against biofilm. It is only 8 cm high, made entirely of stainless steel, and reaches 700 l/h with a discharge head of 24.6 m.

  • Si-1805 (bare ends): centrifugal tank pump for air conditioning and refrigerated display cabinets.

  • Si-1850: large tank pump, up to 1100 l/h, suitable for industrial refrigeration displays. It tolerates charged, high-temperature condensate.

  • Si-83: compact tank pump, also featured for refrigeration applications.

See each product page for the full specifications.

Puddles are most often overflows from a condensate drainage system blocked by pollution (particles, algae, biofilm, sludge). The most common cause is biofilm, which often clogs the drainage tubes upstream of the pump. The condensate must reach the pump reservoir: a pump that resists biofilm is not enough on its own.

Use a non-aggressive anti-biofilm solution such as the Gel Clear tablet supplied with the Si-1931. One tablet can keep the condensate pipes free of blockages for up to a year. The tablet is replaced every six months or every year, depending on climate and cabinet size, and can be inserted while the unit is running.

The tablet is certified non-corrosive for metal and non-aggressive for condensate pumps, it is fully water-soluble, and the formula is approved by NSF International for use in food preparation zones. The Gel Clear safety data sheet can be downloaded from the Si-1931 product page.

Once biofilm has been spotted, it is already too late: the chilled food aisle may have to be closed, the cooling unit switched off and the system deep-cleaned, sometimes for several days. According to Sauermann, 40% of maintenance call-outs on supermarket refrigerated units relate to biofilm, and the Si-1931 with Gel Clear tablet reduces condensate leaks in chilled and frozen food aisles by 95%. A field study by a major Australian retailer showed significant savings on annual maintenance costs.

These pumps should require infrequent maintenance, and be designed to speed up the work of HVACR technicians: connections to the drain tubes that disconnect easily, a pump that opens quickly and preferably without tools, and easy access to the pump core, the filter and the tank. With the Gel Clear solution, maintenance is limited to quick, routine tasks such as replacing the tablet every six months or every year.